INTRODUCTION
SIKUS series AC LV switchboards is a new kind of LV fixed-enclosed power distribution devices with the license issued by Siemens.SIKUS consists of SIKUS Universal and SIKUS Universal HC and be applied in the in the industrial and public field widely.
SIKUS UNIVERSAL
Power distribution up to 3200A in the public or industrial field as main or sec-ondary power distribution switchboards.
degree of protection:IP30¡¢IP41¡¢IP55. |
SIKUS UNIVERSAL HC
Power distribution up to 6400A in the public field as main or secondary power distribution switchboards.
Degree of protection:IP30,IP41.
|
| Characteristics |
* Acomplete range to meet different needs
SIKUS can be applied in the industrial and civil field below 6400A as PCs,feeders and MCCS,etc.
* Leading edge thinking and design.
The Siemens'advanced technology and leading edge appearance design by Giugiaro insure it safe and reliable Whole performance and beautiful appearance
.
* Standard modular structure,perfect fixed/plug-in mounting
The cubicle adopts modular internal separation structure made of galvanized steel sheets and provides excellent mechanical strength.Internal functional units adopting fixed or plug-in mounting kits lead to a fast mounting and simple maintenance.
* Reliable protection and separation
Wall partitions and barriers inside a cubicle provide various forms from form 1 to 4 and degree of protection from IP30 to IP55. |
* Flexibel and reliable busbar system
Main busbar system,rated short time withstand current up to 100kA(1s),can be mounted on the top or the rear to form different power distribution system.
* Advanced reactive power factor compensation devices

Reactive power factor compensation cubicle,with electrc power factor controller with microprocessor,can be operated manually/automatically and also provides RS232 Interface to communicate with PC.
* Intelligent power distribution system
The siemens' ripe technology of automation intellgent switchgear plus on standard open fieldbus s of PROFIBUS-OP can meet the requirements of power management and control and provide stadard interface for BA. |
|
TECHNIAL DATA
|
|
SIKUS Universal |
SIKUS Universal HC |
1 |
Specifications |
IEC604439-1,EN60439-1,VDE0 660-550,GB7251.1-1997 |
2 |
Electrical Data |
3 |
Rated Voltage |
4 |
(Ue) Rated Operation Voltage |
AC400 |
|
5 |
(Ui) Rated Insulation Voltage |
AC690V |
|
6 |
(UimP) Rated Impulse Withsatand Voltage |
8kV |
|
7 |
Class of Overvoltage |
III |
|
8 |
Class of pollution |
3 |
|
9 |
Rated Current |
50/60Hz |
|
10 |
Rated current |
11 |
Horizontal main Busbar |
12 |
(Ie) Rated Operational Current |
3200A |
6400A |
13 |
(Icw) Rated Short-time Withstand Current |
80kA |
100kA |
14 |
(Icw) Rated impulse Withstand Current |
176kA |
220kA |
15 |
Vertical busbar |
16 |
(Ie) Rated Operational Current |
2000A |
3200A |
17 |
(Icw) Rated short-time withstand Current |
80kA |
100kA |
18 |
(Icw) Rated impulse Withstand Current |
176kA |
220kA |
19 |
Mechanical Data |
20 |
Internal Separation Forms |
:1,2,3,4 |
:1,2,3,4 |
21 |
Degree of Protection |
IP30,IP41,IP55 |
IP30,IP41 |
22 |
Dimension |
23 |
Height(mm) |
2200 |
2300 |
24 |
Width(mm) |
700/1000 |
400/600/800/1100+400 |
25 |
Depth(mm) |
600/800/1000 |
1000/1000+400 |
26 |
Surface Treatment |
RAL7035 Clear gray RAL7035 |
27 |
Operational Conditions |
28 |
Ambient Temperature |
5¡ãC¡«40¡ãC |
29 |
Relative Humidity |
90% |
30 |
Altitude |
2000m |
|
NOTES FOR ORDERING
a¡¢Single-line diagrams
b¡¢Control and measuting circuit diagrams(or provided as standards by our factory)
c¡¢The list of components in each board(including type.size.number)
d¡¢The arrangement plan for distribution boards
e¡¢The way of cables entry.
|
|
|